cfr_sections: 40:40:25.0.1.1.4.19.22.27
Data license: Public Domain (U.S. Government data) · Data source: Federal Register API & Regulations.gov API
This data as json
| section_id | title_number | title_name | chapter | subchapter | part_number | part_name | subpart | subpart_name | section_number | section_heading | agency | authority | source_citation | amendment_citations | full_text |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 40:40:25.0.1.1.4.19.22.27 | 40 | Protection of Environment | I | D | 141 | PART 141—NATIONAL PRIMARY DRINKING WATER REGULATIONS | T | Subpart T—Enhanced Filtration and Disinfection—Systems Serving Fewer Than 10,000 People | 141.561 | § 141.561 What happens if my system's turbidity monitoring equipment fails? | EPA | 42 U.S.C. 300f, 300g-1, 300g-2, 300g-3, 300g-4, 300g-5, 300g-6, 300j-4, 300j-9, and 300j-11. | 67 FR 1839, Jan. 14, 2002, unless otherwise noted. | If there is a failure in the continuous turbidity monitoring equipment, your system must conduct grab sampling every four hours in lieu of continuous monitoring until the turbidimeter is back on-line. Your system has 14 days to resume continuous monitoring before a violation is incurred. |